ADAM-6018 8-ch Isolated Thermocouple Input Modbus TCP Module with 8-ch DO
![]() | Right click and choose "Save as" to download the ADAM-6018 data sheet in PDF format. |
![]() | Click here to request a quotation for the ADAM-6018 |
Overview
The ADAM-6018 8-channel thermocouple input module provides 8 thermocouple input channels to support the most popular temperature sensor in today’s industrial automation market. In addition to the 8 T/C input channels, the ADAM-6018 is also equipped with 8 digital output channels for use as auxiliary alarm outputs or pure digital outputs. Last but not least, the ADAM-6018 comes with an external DIN-rail terminal board for wiring between the ADAM-6018 module and the field sensor. This special wiring mechanism greatly enhances the accuracy and reliability for thermocouple measurement in environmental and facility monitoring applications.
Features
- I/O Type: 8 thermocouple Input Channels and 8 Digital Output Channels
- Input type: mV, V, mA
- Supports multi-channel/multi-range
- Supports Type J, K, T, E, R, S and B type thermocouples
- Provide default/customized web page
- Easy mounting on DIN-rail , panel piggyback
- 10/100Based-T Ethernet
- Supports Modbus/TCP
Specifications
Analog Input
- Channels 8 differential
- Resolution 16-bit
- Sampling Rate 10 samples/second
- Input Impedance >10 MΩ
- Input Type Thermocouple
- Input Connection auxilliary DIN rail terminal board
- Input Ranges
- Voltage - ±15mV, ±150mV, ±500mV, ±2.5V
- Current - ±20mA
- Type J - 0-760°C
- Type K - 0-1370°C
- Type T - -100-400°C
- Type E - 0-1000°C
- Type R - 500-1750°C
- Type S - 500-1750°C
- Type B - 500-1800°C
- Accuracy±0.1% or better (voltage)
- Span Drift ±25ppm/°C
- Zero Drift ±6µV/°C
Digital Output
- Channels 8 Open Collector to 30V, 100mA max.load
- Power Dissipation 300mW for each module
Ethernet Communications
- Compatibility IEEE 802.3, IEEE 802.3u
- Speed 10/100 Mbps
- No. of ports 1
- Port Connector 8-pin RJ-45
- Protection Built-in 1.5KV magnetic isolation
General
- Watchdog Timer System (1.6second) and Communication (programmable)
- Supports Peer to Peer mode 1
- Supports Graphical Condition Logic
- Supports Modbus/TCP,TCP/IP,UDP and HTTP Protocols
- Protection
Overvoltage Protection ±35VDC
Isolation Protection 2000VDC - Built-in TVS/ESD Protection
- Power Reversal Protection
Mechanics
- Dimensions (H x W x D) 70 x 130 x 30mm
- Enclosure ABS + PC with solid mounting hardware
- Mounting DIN 35 rail, stack, wall
Power Requirements
- Power Input Unregulated 10 - 30VDC
- Power Consumption 2W @ 24 VDC
Environment
- Operating Temperature -10 to 70°C
- Storage Temperature -20 to 80°C
- Operating Humidity 20 to 95% RH (non-condensing)
- Storage Humidity 0 to 95% RH (non-condensing)